F-gas leak check frequency: how often, and what to record
Leak checks depend on the refrigerant charge in tonnes of CO2 equivalent, not kilograms. Here are the bands, what they mean in kg for the common refrigerants, and the records you have to keep.
In Great Britain, how often a refrigeration, air conditioning or heat pump system must be leak checked depends on how much refrigerant it holds, measured in tonnes of CO2 equivalent (tCO2e): the charge in kilograms multiplied by the refrigerant's global warming potential (GWP), divided by 1,000. The same 5 kg charge can need checking every year with one refrigerant and not at all with another.
The rules come from the F-gas Regulation (EU 517/2014, retained in GB law). DEFRA consulted on reforms in late 2025, but the proposals change the HFC phase-down from 2027, not the leak-check rules below.
Leak check frequency by charge
| Charge | Without leak detection | With automatic leak detection |
|---|---|---|
| Under 5 tCO2e | No mandatory check | No mandatory check |
| 5 to under 50 tCO2e | At least every 12 months | At least every 24 months |
| 50 to under 500 tCO2e | At least every 6 months | At least every 12 months |
| 500 tCO2e or more | Automatic leak detection is required | At least every 6 months |
If a check finds a leak, it must be repaired as soon as possible and the system checked again within one month to confirm the repair worked.
What the bands mean in kilograms
Most engineers think in kilograms on the rating plate, so here are the thresholds for the refrigerants you will meet most on commercial sites.
| Refrigerant | GWP | 5 tCO2e | 50 tCO2e | 500 tCO2e | Typically found in |
|---|---|---|---|---|---|
| R32 | 675 | 7.4 kg | 74 kg | 741 kg | Most new split and VRF air conditioning |
| R410A | 2,088 | 2.4 kg | 24 kg | 239 kg | Split and VRF air conditioning, most installed before about 2020 |
| R407C | 1,774 | 2.8 kg | 28 kg | 282 kg | Older air conditioning and chillers |
| R134a | 1,430 | 3.5 kg | 35 kg | 350 kg | Chillers and medium-temperature refrigeration |
| R404A | 3,922 | 1.3 kg | 13 kg | 127 kg | Older commercial refrigeration and cold rooms |
Who can do the check
Anyone carrying out leak checks, installation, maintenance, servicing or refrigerant recovery on this equipment must hold the appropriate F-gas qualification, and the business they work for must hold an F-gas company certificate from an approved certification body. If you use subcontractors for F-gas work, keep a copy of their company certificate and their engineers' qualifications.
Records you must keep
For every system that needs leak checks, the operator must keep records for at least five years. Where a contractor services the system, they should keep copies too. The record needs:
- The type and quantity of F-gas in the system, and its charge in tCO2e
- Any refrigerant added, and why
- Any refrigerant recovered, and where it went
- Who carried out the work, with their certification
- The date and result of every leak check, and what was done about any leak
Equipment must also carry a clearly visible label showing that it contains F-gas, which gas, the charge in kg, the charge in tCO2e and the gas's GWP.
Running it on a maintenance contract
For a contractor, the work is less the rule than keeping track of it across hundreds of units: knowing which units are in which band, booking each check before it falls due, sending an engineer with the right certificate, and keeping a record you can produce for a client or an auditor five years later.
- Record each unit's refrigerant and charge in your asset register, and work out its tCO2e once.
- Set the leak check interval per unit from the table above, not per site.
- Put the leak check on the job sheet for that unit, with the charge pre-filled and readings to fill in.
- Only send engineers whose F-gas certificate is in date, and keep subcontractors' certificates on file.
- Keep the signed job sheet against the unit, so its full history is in one place.
PPMdesk does this as part of planned maintenance: each unit in the asset register holds its refrigerant and charge, engineers record leak checks on the job sheet, and only certified engineers are offered F-gas work. See how it works for HVAC contractors.
Frequently asked questions
How often does a 5 kg R410A system need a leak check?
5 kg of R410A is 10.4 tCO2e, which is in the 5 to 50 tCO2e band, so it needs a leak check at least every 12 months, or every 24 months if it has automatic leak detection.
Do R32 air conditioning units need F-gas leak checks?
Only if the charge is 7.4 kg or more, which is 5 tCO2e for R32. Many small split systems hold less than that and have no mandatory leak check, although a manufacturer or client may still require one.
How long must F-gas records be kept?
At least five years, by the operator of the equipment. Contractors who service it should keep copies for the same period.
What happens if a leak is found?
It must be repaired as soon as possible, and the system must be checked again within one month to confirm the repair has worked.
- GOV.UK, Checking F gas equipment for leaks
- NetRegs, Stationary refrigeration, air conditioning and heat pumps: F-gas controls
- legislation.gov.uk, Regulation (EU) No 517/2014 as retained